Description
Victron Filax The Ultra-Fast Transfer Switch
Filax 2: the ultra-fast transfer switch The Filax has been designed to switch critical or sensitive loads, such as computers, industrial controls, or modern entertainment equipment from one AC source to another. The priority source typically is the mains, a generator, or shore power. The alternate source typically is an inverter. With its switching time of less than 20 milliseconds sensitive loads will continue to operate without disruption. The Filax is not intended to supply high power household equipment like washing machines, or electric motors.
Open transition transfer The Filax is an open transition (break before make) transfer switch. The maximum load transfer time is 16ms. The load is normally supplied by the priority source, and is transferred to the alternate source if: – The voltage of the priority source drops below the threshold value. – The frequency of the priority source drops below the low frequency threshold value, or increases beyond the high frequency threshold value. Reverse transfer from the alternate source to the priority source is initiated when the priority source has operated within the voltage and frequency reverse switching limits during 30s.
Important Notice: Livestainable relies on the relevant suppliers/manufacturers and/or third-party sellers to provide adequate information displayed on the products we promote on Livestainable.co.za. Therefore, in some cases Errors and Omissions could be expected.
Noticed incorrect information or an issue with this page? Let us know